Earthing explained: what it does, how it is installed and how it is measured

The Journal · Oct 7, 2026

Earthing explained: what it does, how it is installed and how it is measured

Written by Engin Demirel · Electrical technician, master instructor · 12 years of experience

Short answer: Earthing connects the metal bodies of appliances and the earth pin of sockets to the ground through a low-resistance path. In a fault, the voltage on the casing flows away through this path, the RCD or breaker disconnects the circuit and nobody gets a shock. Earthing is provided by a foundation earth, copper-clad rods or tape in the ground, and carried to the consumer unit and sockets by the green-yellow protective conductor. Its resistance is measured with an earth tester, and in RCD-protected homes it must satisfy RA × IΔn ≤ 50 V; in practice the lowest achievable value is targeted. Local rules apply.

What does earthing do?

  • Safety: if the insulation of a metal appliance (washing machine, oven, EV charger) fails, the casing becomes live. Without earthing, the person touching it becomes the current's path.
  • Protective devices: RCDs and breakers trip quickly only when the fault current has a path to earth.
  • Electronics and lightning: surge protectors and lightning protection only work with good earthing.

Earthing systems: TT and TN

  • TT: the building has its own earth electrode and the supply neutral is earthed separately. Fault current returns through the soil; protection relies on the RCD. Common in detached houses and rural areas.
  • TN-C-S / TN-S: the protective conductor is connected to the supplier's earthed neutral. Fault currents are high and breakers can trip quickly. Common in cities and apartment buildings, usually with a foundation earth as well.

The system is determined by the distribution company's connection and the installation design.

What does an earthing system consist of?

PartPurposeTypical installation
Earth electrodePasses current into the groundFoundation earth electrode, copper-bonded rod or tape
Earthing conductorConnects the electrode to the consumer unitCopper conductor or galvanised tape, corrosion-proof joints
Main earthing terminalWhere all protective conductors meetIn the main board, with a removable link for testing
Protective conductor (PE)Carries the earth from sockets and appliance casings to the terminalGreen-yellow cable, sized to the phase conductor
Equipotential bondingBrings metal pipes and parts to the same potentialWater and gas pipes, metal parts in bathrooms

In a new building the best electrode is a foundation earth electrode; see how to install foundation earthing step by step. Colour, size and connection of the protective conductor are covered in earth cable and earthed sockets.

How is earthing installed?

  • Foundation earth: galvanised or copper tape cast into the foundations of new buildings; the best long-term solution.
  • Rod electrodes: copper-clad steel rods driven 1.5–3 m deep; if resistance is too high, several rods are connected, spaced at least one rod length apart.
  • Tape electrodes: copper or galvanised tape laid horizontally 50–80 cm deep.
  • Connection: a green-yellow conductor of suitable size from the electrode to the main earthing terminal; joints are protected from corrosion and left accessible for inspection.
  • Equipotential bonding: water and gas pipes and metal bathroom parts are bonded to the earthing terminal.

Soil type (rocky, sandy, damp) changes the resistance greatly; dry and rocky ground needs more electrodes.

What earth resistance is acceptable?

  • In an RCD-protected TT system: RA × IΔn ≤ 50 V. With a 30 mA RCD this theoretically allows a very high value (1,666 Ω), but because resistance varies with moisture and season, much lower values are targeted in practice.
  • Lightning protection systems usually require 10 Ω or less.
  • The exact limit depends on the installation type and design.

Earth resistance table: how many ohms in which case?

In installations protected by RCDs (TT system), the basic rule is that the touch voltage on a faulty casing must not exceed 50 V: RA × IΔn ≤ 50 V. This gives the maximum resistance; because measured values rise as soil dries and with the seasons, much lower values are targeted in practice.

CaseMaximum by calculationIn practice
30 mA RCD50 V ÷ 0.03 A ≈ 1,666 ΩMuch lower to allow for seasonal change and ageing; as low as practical
300 mA RCD50 V ÷ 0.3 A ≈ 166 ΩLower values targeted
Lightning protectionPer designUsually 10 Ω or less
TN system (urban supply)Loop impedance is measured, not electrode resistanceThe fuse or breaker must trip fast enough on a fault
EV chargerDepends on the system (TT/TN)Chargers refuse to start on an earth fault; test before installation

The exact limit depends on the type of installation, the protective device and local rules; testing and assessment should be done by a qualified electrician.

How is earthing measured?

With an earth resistance tester using two auxiliary stakes (three-pole method) or a clamp-type tester. Plug-in socket testers only show whether earth is connected, not its resistance. Workplaces typically have earthing tested periodically (often yearly) by qualified persons, with a report.

Earth resistance testing step by step (three-pole method)

  1. Preparation: the earth electrode being tested (rod or foundation earth) is disconnected from the main earthing terminal; otherwise the reading includes the other connections of the installation. This is done with the supply switched off.
  2. Current spike: an auxiliary spike for the current lead (H or C) of the earth tester is driven about 20–40 m away from the electrode.
  3. Voltage spike: a second spike for the voltage lead (S or P) is driven in line, at about 62% of the distance between the electrode and the current spike.
  4. Measurement: the E lead goes to the electrode, H and S to the auxiliary spikes, and the resistance is read.
  5. Check: move the voltage spike a few metres forwards and backwards and repeat. If the readings are close the result is valid; if they differ widely, move the current spike further away.
  6. Record: write down the date, value, soil condition (dry/wet) and instrument, then reconnect the electrode.

Where spikes cannot be driven (concrete, city centres) a clamp-on tester is used; it measures without disconnecting the electrode but only works where there are several earth paths.

What is earth enhancement material and how is it used?

Earth enhancement material (often bentonite- or carbon-based "ground enhancement compound") is packed around the electrode to improve soil conductivity and lower resistance. It helps in rocky, sandy and dry soil, but does not replace extra electrodes or depth.

  1. Dig a hole for the rod or a trench for the tape (typically 30–50 cm wide).
  2. Mix the compound with water in the ratio given by the manufacturer to a slurry.
  3. Place the electrode and pour the mixture so it fully surrounds it.
  4. Once it has set, backfill with the excavated soil and compact it.
  5. Measure the earth resistance again after a while.

"Wetting" the soil with salt, charcoal or chemicals is an old method; it corrodes the electrode and the effect is short-lived, so it is not recommended.

When are an earthing design and a test report needed?

  • New buildings and renovations: earthing is part of the electrical installation design; foundation earthing is laid before the concrete is poured.
  • Substations, industrial sites, large businesses: a separate earthing calculation and design is prepared.
  • Workplaces: earth resistance is usually tested periodically (commonly once a year) and recorded by a qualified person; the report is requested in safety inspections.
  • Homes: there is often no mandatory periodic test, but testing is advisable before installing an EV charger, heat pump or solar system and if the RCD trips often.

A test report records the date, the electrode and value measured, the instrument and its calibration, the method and who carried out the test.

Earthing and EV chargers

The charger body and the car's chassis are connected to the protective conductor. Many chargers will not start charging if earthing is missing or poor. Earthing is measured before installation and improved if needed; the charging circuit is also protected by a type B RCD or 6 mA DC leakage detection.

Earthing and testing must be done by a qualified electrician. In Bursa, ENGN provides earthing, electrical installation and EV charger installation.

Frequently asked questions

What does earthing do?

It carries fault voltage on an appliance casing to ground, so the RCD or breaker disconnects the circuit and nobody gets a shock.

What earth resistance is acceptable?

In an RCD-protected TT system RA × IΔn ≤ 50 V must be met, with the lowest practical value targeted. Lightning protection usually needs 10 Ω or less.

How is earth resistance measured?

With an earth tester using two auxiliary stakes, or a clamp-type tester. Plug-in testers only show that earth is connected, not its resistance.

How is a house earthed?

With a foundation earth, copper-clad rods or horizontal tape in the ground, connected by a green-yellow conductor to the main earthing terminal.

Can an EV charger be installed without earthing?

No. The charger and the car's chassis must be earthed; many chargers will not start without a proper earth.

How often should earthing be tested?

Workplaces typically test it periodically, often yearly. At home, test it when the installation changes or a large load such as an EV charger is added.

Can you test earthing from a socket?

The resistance of the earth electrode cannot be measured at a socket. Installation testers can measure the earth fault loop impedance at a socket and show whether earth is connected; the electrode's resistance itself is measured with an earth tester.

Can you test earthing with a multimeter?

A multimeter does not measure earth resistance, and the ohms range must never be used on a live circuit. It can only check voltages: if live-to-earth is about the same as live-to-neutral (230 V), earth is connected, and neutral-to-earth is only a few volts. This check and the measurement should be done by a qualified electrician.

What is earthing?

Earthing connects metal casings and the earth pins of sockets to the ground through a low-resistance path. In a fault, current flows this way, the RCD or breaker disconnects the circuit and people are protected from electric shock.

What does an earthing system consist of?

An earth electrode (foundation earth, rod or tape), the earthing conductor to the board, the main earthing terminal, green-yellow protective conductors to sockets and appliances, and equipotential bonding of metal pipes.

Does earth enhancement compound work?

Yes, packed around the electrode it lowers earth resistance in rocky, sandy and dry soil. It does not replace more or deeper electrodes, and the resistance should be measured again afterwards.

What is an earth resistance test report?

A document in which a qualified person records the measured earth resistance with date, value, method and instrument details. Workplaces usually need one periodically, commonly once a year.

When is an earthing design needed?

In new buildings earthing is part of the electrical installation design. Substations, industrial sites and large businesses get a separate earthing calculation and design.