Cable size calculation: current capacity and voltage drop (with examples)

The Journal · Oct 7, 2026

Cable size calculation: current capacity and voltage drop (with examples)

Written by Engin Demirel · Electrical technician, master instructor · 12 years of experience

Short answer: A cable size is chosen to meet two conditions: it must carry the circuit current without overheating (current-carrying capacity), and the voltage drop along the run must stay below the limit. Single-phase voltage drop is %e = (2 × L × P × 100) ÷ (k × S × U²), three-phase %e = (L × P × 100) ÷ (k × S × U²), with L in metres, P in watts, S in mm², k = 56 for copper and U = 230 V single-phase or 400 V three-phase. IEC 60364-5-52 recommends about 3% for lighting and 5% for other uses from the supply origin; some countries are stricter (Turkey: 1.5% lighting, 3% power). Whichever condition needs the larger cable wins.

1. Current-carrying capacity

The cable must carry more than the circuit breaker rating. Common pairings in home wiring:

  • 1.5 mm² → 10 A (lighting)
  • 2.5 mm² → 16 A (sockets)
  • 4 mm² → 20–25 A
  • 6 mm² → 32 A
  • 10 mm² → 40–50 A

Installation in conduit, grouping and hot surroundings reduce these values (correction factors); the exact figure comes from the cable manufacturer's tables and the installation method.

2. Voltage drop

On long runs, voltage drops even when the capacity is sufficient: lights dim, motors struggle and chargers reduce power or report faults.

  • Single-phase: %e = (2 × L × P × 100) ÷ (k × S × U²), U = 230 V
  • Three-phase: %e = (L × P × 100) ÷ (k × S × U²), U = 400 V
  • k = 56 for copper, 35 for aluminium.

Example 1: 7.4 kW single-phase charger, 25 m

P = 7,400 W, L = 25 m, S = 6 mm²: %e = (2 × 25 × 7,400 × 100) ÷ (56 × 6 × 230²) = 37,000,000 ÷ 17,774,400 ≈ 2.1%

Within a 3% limit. At 40 m the same circuit gives 3.3%; 10 mm² brings it down to 2%. For charging circuits, aim below 3% and lower where possible, because charging runs at full load for hours.

Example 2: 11 kW three-phase charger, 30 m

P = 11,000 W, L = 30 m, S = 4 mm²: %e = (30 × 11,000 × 100) ÷ (56 × 4 × 400²) = 33,000,000 ÷ 35,840,000 ≈ 0.9%

Three-phase carries the same power at lower current, so the drop is small; here current capacity (16 A → 2.5–4 mm²) decides the size.

Example 3: Garden lighting, 230 V, 60 m, 300 W

S = 1.5 mm²: %e = (2 × 60 × 300 × 100) ÷ (56 × 1.5 × 52,900) = 3,600,000 ÷ 4,443,600 ≈ 0.8% — fine. In 12–24 V low-voltage systems U is very small, so voltage drop grows fast; the same power needs much thicker cable or several drivers.

Points to watch

  • Length is the actual cable length from the consumer unit to the last device, including vertical runs.
  • Larger cables must fit the terminals; a big cable will not fit a small terminal.
  • Drop on the main supply cable (meter to consumer unit) adds to the total.
  • The calculation is a guide; the installation design and a qualified electrician make the final choice.

In Bursa, ENGN provides cable sizing and installation for EV charging circuits, electrical installations and outdoor lighting.

Frequently asked questions

How do I calculate cable size?

Check current-carrying capacity for the circuit current, then voltage drop for the run length; choose whichever needs the larger cable.

What is the voltage drop formula?

Single-phase: %e = (2 × L × P × 100) ÷ (k × S × U²); three-phase: %e = (L × P × 100) ÷ (k × S × U²). k = 56 for copper; U = 230 V or 400 V.

What voltage drop is allowed?

IEC 60364-5-52 recommends about 3% for lighting and 5% for other uses; national rules may be stricter (Turkey: 1.5% lighting, 3% power).

What cable size for a 7.4 kW EV charger?

At least 6 mm² for 32 A. At 25 m the drop is about 2.1%; from 40 m, 10 mm² is preferred.

What cable size for an 11 kW three-phase charger?

Usually 5 × 2.5–4 mm² for 3 × 16 A; at 30 m with 4 mm² the drop is about 0.9%.

Is aluminium cable different from copper?

Yes; aluminium conducts less (k = 35 vs 56 for copper), so it needs a larger cross-section for the same current and drop.