November: 20% off + 6 instalments at cash price

Cable size calculation: what cable size for how many kW? (with examples)

The Journal · Oct 7, 2026

Cable size calculation: what cable size for how many kW? (with examples)

Written by Engin Demirel · Electrical technician, master instructor · 12 years of experience

Short answer: A cable size is chosen to meet two conditions: it must carry the circuit current without overheating (current-carrying capacity), and the voltage drop along the run must stay below the limit. Single-phase voltage drop is %e = (2 × L × P × 100) ÷ (k × S × U²), three-phase %e = (L × P × 100) ÷ (k × S × U²), with L in metres, P in watts, S in mm², k = 56 for copper and U = 230 V single-phase or 400 V three-phase. IEC 60364-5-52 recommends about 3% for lighting and 5% for other uses from the supply origin; some countries are stricter (Turkey: 1.5% lighting, 3% power). Whichever condition needs the larger cable wins.

1. Current-carrying capacity

The cable must carry more than the circuit breaker rating. Common pairings in home wiring:

  • 1.5 mm² → 10 A (lighting)
  • 2.5 mm² → 16 A (sockets)
  • 4 mm² → 20–25 A
  • 6 mm² → 32 A
  • 10 mm² → 40–50 A

Installation in conduit, grouping and hot surroundings reduce these values (correction factors); the exact figure comes from the cable manufacturer's tables and the installation method.

2. Voltage drop

On long runs, voltage drops even when the capacity is sufficient: lights dim, motors struggle and chargers reduce power or report faults.

  • Single-phase: %e = (2 × L × P × 100) ÷ (k × S × U²), U = 230 V
  • Three-phase: %e = (L × P × 100) ÷ (k × S × U²), U = 400 V
  • k = 56 for copper, 35 for aluminium.

The formula, percentage limits and maximum run tables by cable size are explained in voltage drop calculation.

Cable size by kW: quick list

First convert power to current: single-phase I = P ÷ 230, three-phase I = P ÷ (1.73 × 400). The values below are common practice for copper cable in conduit and a short run (up to roughly 20–25 m); loads with a low power factor such as motors draw slightly more current.

Single-phase (230 V):

  • 1–2 kW (about 4–9 A) → 1.5 mm², 10 A breaker
  • 3–3.7 kW (about 13–16 A) → 2.5 mm², 16 A breaker
  • 4.6 kW (about 20 A) → 4 mm², 20 A breaker
  • 5.5 kW (about 24 A) → 4 mm², 25 A breaker
  • 7.4 kW (about 32 A) → 6 mm², 32 A breaker
  • 9.2 kW (about 40 A) → 10 mm², 40 A breaker

Three-phase (400 V, 5-core cable):

  • 5 kW (about 7 A) → 5 × 1.5 mm², 10 A breaker
  • 7.5–11 kW (about 11–16 A) → 5 × 2.5 mm², 16 A breaker
  • 15 kW (about 22 A) → 5 × 4 mm², 25 A breaker
  • 22 kW (about 32 A) → 5 × 6 mm², 32 A breaker
  • 30 kW (about 43 A) → 5 × 10 mm², 50 A breaker

On longer runs voltage drop decides. Approximate maximum run lengths from the formula with a 3% limit:

  • 3.7 kW single-phase: ~30 m with 2.5 mm², ~48 m with 4 mm²
  • 7.4 kW single-phase: ~36 m with 6 mm², ~60 m with 10 mm²
  • 11 kW three-phase: ~61 m with 2.5 mm², ~98 m with 4 mm²
  • 22 kW three-phase: ~73 m with 6 mm²

Beyond these lengths, go up one size. The list is a guide only; installation method, ambient temperature and cable type change the values, local wiring rules apply and a qualified electrician makes the final choice.

Example 1: 7.4 kW single-phase charger, 25 m

P = 7,400 W, L = 25 m, S = 6 mm²: %e = (2 × 25 × 7,400 × 100) ÷ (56 × 6 × 230²) = 37,000,000 ÷ 17,774,400 ≈ 2.1%

Within a 3% limit. At 40 m the same circuit gives 3.3%; 10 mm² brings it down to 2%. For charging circuits, aim below 3% and lower where possible, because charging runs at full load for hours.

Example 2: 11 kW three-phase charger, 30 m

P = 11,000 W, L = 30 m, S = 4 mm²: %e = (30 × 11,000 × 100) ÷ (56 × 4 × 400²) = 33,000,000 ÷ 35,840,000 ≈ 0.9%

Three-phase carries the same power at lower current, so the drop is small; here current capacity (3 × 16 A → 5 × 2.5 mm²; the 4 mm² in the example adds margin) decides the size.

Example 3: Garden lighting, 230 V, 60 m, 300 W

S = 1.5 mm²: %e = (2 × 60 × 300 × 100) ÷ (56 × 1.5 × 52,900) = 3,600,000 ÷ 4,443,600 ≈ 0.8% — fine. In 12–24 V low-voltage systems U is very small, so voltage drop grows fast; the same power needs much thicker cable or several drivers.

Points to watch

  • Length is the actual cable length from the consumer unit to the last device, including vertical runs.
  • Larger cables must fit the terminals; a big cable will not fit a small terminal.
  • Drop on the main supply cable (meter to consumer unit) adds to the total.
  • The calculation is a guide; the installation design and a qualified electrician make the final choice.

In Bursa, ENGN provides cable sizing and installation for EV charging circuits, electrical installations and outdoor lighting.

Frequently asked questions

How do I calculate cable size?

Check current-carrying capacity for the circuit current, then voltage drop for the run length; choose whichever needs the larger cable.

What is the voltage drop formula?

Single-phase %e = (2 × L × P × 100) ÷ (k × S × U²), three-phase %e = (L × P × 100) ÷ (k × S × U²); explanation and examples in [voltage drop calculation](/en/journal/voltage-drop-calculation).

What voltage drop is allowed?

IEC 60364-5-52 recommends about 3% for lighting and 5% for other uses; national rules may be stricter (Turkey: 1.5% lighting, 3% power); details in [voltage drop calculation](/en/journal/voltage-drop-calculation).

What cable size for a 7.4 kW EV charger?

At least 6 mm² for 32 A. At 25 m the drop is about 2.1%; from 40 m, 10 mm² is preferred.

What cable size for an 11 kW three-phase charger?

Usually 5 × 2.5–4 mm² for 3 × 16 A; at 30 m with 4 mm² the drop is about 0.9%.

Is aluminium cable different from copper?

Yes; aluminium conducts less (k = 35 vs 56 for copper), so it needs a larger cross-section for the same current and drop.

What cable size do I need for 3 kW?

Single-phase 3 kW draws about 13 A; on a short run 2.5 mm² cable with a 16 A breaker is enough. For runs over about 30 m, consider 4 mm² because of voltage drop.

What cable size is used for 5 kW?

Single-phase 5 kW is about 22 A, so 4 mm² cable with a 25 A breaker is used. Three-phase, the same power is about 7 A per phase and 5 × 1.5 mm² is enough.

What cable size do I need for 22 kW?

22 kW three-phase draws about 32 A per phase; 5 × 6 mm² copper cable with a 32 A breaker is common practice. For runs over roughly 70 m, 10 mm² is preferred.